¹þ¹þÌåÓý¡¤(haha)Ê®ÄêÔËÓª,ÐÅÓþÎÞÓÇ-È«Íø×îȨÍþµÄ×ãÇòƽ̨

  • Challenges
    Renewable integration challenges due to insufficient energy storage and grid flexibility.
    Grid strain from supply-demand imbalance, caused by inadequate peak-shaving and frequency regulation capabilities.
    High grid infrastructure upgrade costs due to constrained transmission and distribution (T&D) capacity.
    Solutions
    Functions
    Features primary frequency response and AGC/AVC capabilities for rapid response to grid dispatch commands for peak-shaving and frequency regulation.
    Performs energy arbitrage to mitigate price volatility and optimize supply-demand balance.
    Supports black-start capability for critical grid restoration.
    Benefits
    Maximized revenue streams through participating in medium-to-long-term trading, spot markets, and ancillary services.
    Enhances renewable energy integration and expands the grid flexible resources.
    Optimized grid capability through strengthened transmission and distribution (T&D) capacity, and deferred infrastructure investment.
    Advantages
    Safety

    Multi-stage fuse protection with millisecond-level coordinated response and real-time insulation monitoring.

    Intelligent three-level fire alarm mechanism with pack-level detection and water suppression system.

    Real-time thermal runaway monitoring with multi-layers pressure release and explosion proof protection.

    Cost Efficiency

    Long-life LFP batteries with high-precision SOX algorithms that maximize return on investment.

    Up to 88% system RTE with ¡Ý93% DC-side efficiency.

    Intelligent liquid-cooling system that maintains cell operation temp ¡Ü35 ¡ãC with ¡Ü3 ¡ãC temp control, reducing auxiliary power consumption by 10%.

    Reliability

    AI-driven predictive maintenance enables fault forecasting, reducing unplanned outages by 90%.

    Remote fault diagnostics and OTA upgrades, resolving over 90% of issues online.

    Modular design reduces key components replacement time and improves maintenance efficiency.

    TECHNICAL DATA
    ITEM SPECIFICATIONS
    Cell capacity LFP 314Ah
    System configuration 12P*416S
    Voltage range 1164.8~1497.6Vdc
    Charge/discharge rate 0.5P
    Nominal energy 5.015MWh
    Nominal power 2.508MW
    Dimensions (WxDxH) 6058x2438x2896mm
    Weight <42.5t
    Round-trip efficiency ¡Ý93%
    Protection level IP55 (Battery compartment)
    Cooling method Intelligent liquid cooling
    Fire protection system Aerosol+Water fire suppression
    Communication CAN/RS485/Ethernet
    Operating temp. range -30¡ãC~50¡ãC (Derated at -45¡ãC)
    Storage humidity 0~95% (Non-condensing)
    Noise ¡Ü75dBA
    Max. Operating altitude 4000m (Derated at 2000m)
    ¡¾ÍøÕ¾µØÍ¼¡¿¡¾sitemap¡¿